4.1 Working with iocsh: Script Files and Commands

In previous chapters, we configured our IOCs directly within the main startup script, typically st.cmd. While this approach is functional for simple IOCs, it can become difficult to manage as configurations grow more complex or when multiple similar devices need to be configured.

This section introduces a more modular and maintainable approach used within the ALS-U EPICS Environment: encapsulating specific configuration tasks into reusable iocsh script files (often saved with a .iocsh extension). These snippet files contain standard iocsh commands but are designed to be called from the main st.cmd using the iocshLoad command. This allows for parameterization via macros.

Motivation: Why Use Snippet Files?

Creating reusable iocsh script files offers several advantages:

  1. Modularity: Breaks down complex configurations into smaller, manageable units.
  2. Reusability: The same snippet can be used multiple times with different parameters (e.g., configuring several identical devices).
  3. Clarity: Keeps the main st.cmd cleaner and focused on the overall IOC structure and loading necessary components.
  4. Maintainability: Changes to a specific device configuration only need to be made in one snippet file, rather than potentially multiple places in a large st.cmd.
  5. Standardization: Encourages consistent configuration patterns across different IOCs.

Example: Refactoring st.cmd

Let’s look at the example you provided, converting a direct configuration into one using a reusable snippet.

Original Approach (st.cmd)

Here, the Asyn port configuration and database loading are done directly in the main script:

## st.cmd
...

epicsEnvSet("DB_TOP", "$(TOP)/db")

epicsEnvSet("PREFIX_MACRO", "jeonglee:")
epicsEnvSet("DEVICE_MACRO", "myoffice:")

epicsEnvSet("ASYN_PORT_NAME", "LocalTCPServer")
epicsEnvSet("TARGET_HOST",    "127.0.0.1")
epicsEnvSet("TARGET_PORT",    "9399")
...
drvAsynIPPortConfigure("$(ASYN_PORT_NAME)", "$(TARGET_HOST):$(TARGET_PORT)", 0, 0, 0)
...
asynOctetSetInputEos("$(ASYN_PORT_NAME)", 0, "\n") 
asynOctetSetOutputEos("$(ASYN_PORT_NAME)", 0, "\n") 
...
dbLoadRecords("$(DB_TOP)/training.db", "P=$(PREFIX_MACRO),R=$(DEVICE_MACRO),PORT=$(ASYN_PORT_NAME)")

...

Refactored Approach (st2.cmd + training_device.iocsh)

Now, the main script (st2.cmd) defines some parameters and then calls a separate snippet file (training_device.iocsh) to perform the actual configuration.

  • st2.cmd
...
epicsEnvSet("DB_TOP", "$(TOP)/db")
epicsEnvSet("IOCSH_LOCAL_TOP",  "$(TOP)/iocsh")

epicsEnvSet("PREFIX_MACRO", "jeonglee:")
epicsEnvSet("DEVICE_MACRO", "myoffice:")
...
epicsEnvSet("ASYN_PORT_NAME",   "LocalTCPServer")

iocshLoad("$(IOCSH_LOCAL_TOP)/training_device.iocsh", "PREFIX=$(PREFIX_MACRO),DEVICE=$(DEVICE_MACRO),DATABASE_TOP=$(DB_TOP),PORT_NAME=$(ASYN_PORT_NAME)")
...
  • training_device.iocsh in jeonglee-DemoApp/iocsh:
####################################################################################################
############ START of training_device.iocsh ########################################################
#-- PREFIX         :
#-- DEVICE         : 
#-- DATABASE_TOP   :
#-- PORT_NAME      :
#-- HOST           : [Default] 127.0.0.1
#-- PORT           : [Default] 9399 
#-- ASYNTRACE      : [Default] ##-
#--#################################################################################################
#--#
#--#

#-- Configure the Asyn IP port using the parameters defined above
#-- drvAsynIPPortConfigure("portName", "host:port", priority, noAutoConnect, noProcessEos)
#-- priority=0 (default), noAutoConnect=0 (connect immediately), noProcessEos=0 (use Asyn default EOS processing)
drvAsynIPPortConfigure("$(PORT_NAME)", "$(HOST=127.0.0.1):$(PORT=9399)", 0, 0, 0)

#-- Configure End-of-String (EOS) terminators for the Asyn port layer
#-- These define how messages are delimited when reading from/writing to the port.
#-- Ensure these match the actual device/simulator protocol! (\n = newline, \r = carriage return)
#-- NOTE: While EOS can sometimes be defined within the StreamDevice protocol file (.proto),
#-- for long-term maintenance, it is often considered best practice to define port-specific
#-- behavior like EOS explicitly in the st.cmd file using Asyn commands.
#-- Input EOS (what character(s) mark the end of a message *received from* the device)
asynOctetSetInputEos("$(PORT_NAME)", 0, "\n")
#-- Output EOS (what character(s) should be *appended to* messages *sent to* the device)
asynOctetSetOutputEos("$(PORT_NAME)", 0, "\n")

$(ASYNTRACE=#--)asynSetTraceMask($(PORT_NAME), -1, ERROR|FLOW|DRIVER)

#-- --- Load Database Records ---
dbLoadRecords("$(DATABASE_TOP)/training.db", "P=$(PREFIX),R=$(DEVICE),PORT=$(PORT_NAME)")
#-- --- End Record Load ---

############ END of training_device.iocsh ##########################################################
####################################################################################################

Key Concepts Explained

Let’s break down how this refactoring works:

1. Defining Snippet Location

In st2.cmd, epicsEnvSet("IOCSH_LOCAL_TOP", "$(TOP)/iocsh") defines a standard location for these reusable script files relative to the application top directory. This makes the iocshLoad paths cleaner.

2. The iocshLoad Command

This command is the core mechanism for executing commands from another file. Its basic syntax is:

iocshLoad("path/to/training_device.iocsh", "MACRO1=VALUE1,MACRO2=VALUE2,...")

  • The first argument is the path to the snippet file. Using variables like $(IOCSH_LOCAL_TOP) makes paths relative and portable.
  • The second argument is a comma-separated string of MACRO=VALUE pairs. These macros ($(MACRO1), $(MACRO2), etc.) become available for substitution wherever $(MACRO) appears within the loaded snippet.iocsh file.
  • The VALUE part can itself be a literal string, an environment variable ($(ENV_VAR) set via epicsEnvSet), or even another macro defined earlier in the calling script. In the example, PORT_NAME=$(ASYN_PORT_NAME) uses the value of the ASYN_PORT_NAME environment variable to define the PORT_NAME macro for the snippet.

3. Snippet File (*.iocsh) Structure

  • Parameters: Uses $(MACRO) syntax (e.g., $(PORT_NAME), $(PREFIX)) to receive values passed via iocshLoad.

  • Defaults: $(MACRO=DEFAULT) syntax provides a fallback value if the macro isn’t passed (e.g., $(HOST=127.0.0.1)).

  • Documentation: Clear comments explaining the purpose and required/optional macros are crucial for reusability.

  • Conditional Logic: The $(ASYNTRACE=#--) trick provides simple conditional execution – if ASYNTRACE is defined in the iocshLoad call (even if empty, like ASYNTRACE=), the line runs; otherwise, it becomes a comment.

  • Consistency Note: Inside training_device.iocsh, commands related to the Asyn port now consistently use the $(PORT_NAME) macro, which receives its value from the iocshLoad call. This ensures the snippet correctly references the port name it’s supposed to configure.

Useful EPICS IOC shell commands

Even when using snippet files, the underlying commands are standard iocsh commands. You can still interact with the running IOC using the shell for debugging:

  • dbl: List loaded record types, simply EPICS PV (signal) list
  • dbpr("recordName", interestLevel): Print record (signal) details.
  • epicsEnvShow : Print value of an environment variable, or all variables.
  • help: List available commands.
  • exit: Exit the IOC shell (usually stops the IOC).

Exercise: Refactor Your Simulator Configuration

Now, apply this technique to the IOC configuration you created in Chapter 3 for the TCP simulator:

  1. Create Snippet File: Create a new file, for example, $(TOP)/jeonglee-DemoApp/iocsh/training_device.iocsh.
  2. Move Commands: Identify the drvAsynIPPortConfigure, asynOctetSet*Eos, and dbLoadRecords commands related to your simulator in your Chapter 3 st.cmd file and move them into training_device.iocsh.
  3. Parameterize: Replace hardcoded values (like PV prefix, device name, port name, host, port) in the snippet file with $(MACRO) variables. Add documentation comments explaining the macros. Provide defaults for host (127.0.0.1) and port (9399).
  4. Define Location: In your main st.cmd, ensure IOCSH_LOCAL_TOP is defined (e.g., epicsEnvSet("IOCSH_LOCAL_TOP", "$(TOP)/iocsh")).
  5. Modify st.cmd: Remove the original commands you moved and add an iocshLoad command to call your new training_device.iocsh, passing the required macros (e.g., PREFIX=$(MY_PREFIX), DEVICE=$(MY_DEVICE_NAME), PORT_NAME=$(SIM_PORT_NAME) etc., using appropriate variable names from your st.cmd).
  6. Build: After creating or modifying the training_device.iocsh file in your source directory, run make in your application’s top-level directory. This command typically copies your .iocsh file from its source location (e.g., jeonglee-DemoApp/iocsh/) to the runtime iocsh folder (e.g., $(TOP)/iocsh) where the IOC expects to find it via $(IOCSH_LOCAL_TOP) or a similar path during startup.
  7. Test: Run the IOC from its runtime directory (e.g., iocBoot/iocB46-182-jeonglee-Demo). It should start and communicate with the simulator exactly as before, but now using the cleaner, modular structure.

An example of st2.cmd

Here is the example of the full st2.cmd.

#!../../bin/linux-x86_64/jeonglee-Demo


#-- Load environment paths (sets TOP, EPICS_BASE etc.)
#-- It will be generated during the building process.
< envPaths

#-- Set a variable for the top-level db directory where .db and .proto files reside during runtime
#-- Note that this is the installed $(TOP)/db folder, not the source <APPNAME>App/Db folder.
epicsEnvSet("DB_TOP", "$(TOP)/db")

#-- Set the path where StreamDevice should look for protocol (.proto) files
epicsEnvSet("STREAM_PROTOCOL_PATH", "$(DB_TOP)")

#-- Set a variable for the top-level iocsh directory
epicsEnvSet("IOCSH_LOCAL_TOP",      "$(TOP)/iocsh")
#-- --- Define Macros for dbLoadRecords ---
#-- Define the Prefix macro value (substituted for $(P) in .db files)
epicsEnvSet("PREFIX_MACRO", "jeonglee:")
#-- Define the Record/Device macro value (substituted for $(R) in .db files)
epicsEnvSet("DEVICE_MACRO", "myoffice:")
#-- --- End Macros ---

#-- Standard IOCNAME and IOC settings
#-- These EPICS IOC variables were defined by the template generator,
#-- since these two variables are out-standing badly confusing variables
#-- through EPICS history, please don't change if you have the very specific reasons
#-- if your IOC within the ALS-U Controls Production Enviornment.
epicsEnvSet("IOCNAME", "B46-182-jeonglee-Demo")
epicsEnvSet("IOC", "iocB46-182-jeonglee-Demo")

#-- Load the compiled database definitions (.dbd file generated by build)
#-- Path is relative to TOP directory.
dbLoadDatabase "$(TOP)/dbd/jeonglee-Demo.dbd"
#-- Register device and driver support compiled into the IOC application
jeonglee_Demo_registerRecordDeviceDriver pdbbase

#-- Change directory to the IOC's specific boot directory (standard practice before iocInit)
cd "${TOP}/iocBoot/${IOC}"

#-- --- Asyn IP Port Configuration ---
#-- Define connection parameters for the Asyn port we will create
epicsEnvSet("ASYN_PORT_NAME", "LocalTCPServer") # Logical name for this Asyn port
epicsEnvSet("TARGET_HOST",    "127.0.0.1")      # IP address of the target device/simulator
epicsEnvSet("TARGET_PORT",    "9399")           # TCP port of the target device/simulator

#-- --- iocshLoad Configuration examples --- 
iocshLoad("$(IOCSH_LOCAL_TOP)/training_device.iocsh", "PREFIX=$(PREFIX_MACRO),DEVICE=$(DEVICE_MACRO),DATABASE_TOP=$(DB_TOP),PORT_NAME=$(ASYN_PORT_NAME)")
#--iocshLoad("$(IOCSH_LOCAL_TOP)/training_device.iocsh", "PREFIX=$(PREFIX_MACRO),DEVICE=$(DEVICE_MACRO),DATABASE_TOP=$(DB_TOP),PORT_NAME=$(ASYN_PORT_NAME), HOST=$(TARGET_HOST), PORT=$(TARGET_PORT)")
#--iocshLoad("$(IOCSH_LOCAL_TOP)/training_device.iocsh", "PREFIX=$(PREFIX_MACRO),DEVICE=$(DEVICE_MACRO),DATABASE_TOP=$(DB_TOP),PORT_NAME=$(ASYN_PORT_NAME), HOST=$(TARGET_HOST), PORT=$(TARGET_PORT), ASYNTRACE=")

#-- Initialize the IOC
#-- This command starts record processing, enables Channel Access connections, etc.
#-- It MUST come *after* all hardware (Asyn port) configuration and record loading.
iocInit

#-- --- Optional Post-Initialization Commands ---
#-- Add any commands to run after the IOC is fully initialized, for example:
ClockTime_Report #-- Example site-specific utility
#-- --- End Post-Init ---

Assignments or Questions for the further understanding.

  • We defined TARGET_HOST in st2.cmd, however we never use it. Can you explain why?
  • In the st2.cmd, we have three different exmaples for iocshload usages. Please test it one by one, and see what different among them.
  • Complete command out iocshload with #. Restart your ioc, then can you see what happens? This is a way to disable one device communication within st2.cmd effectively. We will discuss this later with real example.

Considerations

As you noted, there are some challenges when adopting this approach, especially for beginners:

  1. Initial Complexity: Designing truly generic, reusable iocsh files that handle various device or system configurations requires careful planning and understanding of potential variations.
  2. Variable/Macro Scope: Keeping track of variable names and macro definitions across different files (st.cmd, *.iocsh snippets, database substitution files (.substitutions), database template files (.template)) can be challenging initially. Understanding where each variable/macro is defined and used is key. (Database templates/substitutions will be covered in Section Database Templates and Substitution).

Conclusion

Using iocshLoad and creating dedicated *.iocsh snippet files represents a best practice within the ALS-U EPICS Environment for managing IOC configurations. While it introduces some initial complexity compared to editing a single st.cmd, the long-term benefits in modularity, reusability, clarity, and maintainability are substantial, especially for complex systems. Mastering this technique is a key step towards developing robust and professional EPICS applications.